Skip to main content

Energy MonitoringPower Quality

Power quality faults damage equipment long before anything reaches the bill

Voltage sags, phase imbalance, harmonics and poor power factor do their work quietly: motors that fail early, drives that trip for no stated reason, and charges on the bill nobody has traced. None of this reaches a monthly statement. It is visible only in continuous measurement at the distribution board, where every event carries a timestamp you can set against a production record.

Start from the symptom your team already reports

The work starts from the fault your engineers keep reporting, then measures whether the suspected cause is the actual cause. The table below is the route from one to the other.

Reported symptom, likely cause, and the measurement that confirms or rules it out
What you observeWhat it usually indicatesWhat we measure to confirm it
Motors and drives failing earlier than they shouldSustained voltage imbalance or harmonic heating in the windings. Rarely one dramatic event, usually years of small ones.Per-phase voltage and current logged continuously, phase imbalance calculated across the campaign, harmonic distortion measured at the affected feeders.
Breakers and drives tripping with no obvious causeVoltage sags on the incoming supply, or a start-up inrush colliding with another load. Very often recorded as operator error because nothing was measuring.Event logging with timestamps at the incomer and the affected board, correlated against your production or operations log.
Billed capacity higher than the work the plant is doingMaximum demand is billed in kVA, not in kW. A plant drawing 800 kW at 0.95 power factor is billed on 842 kVA; the same 800 kW at 0.80 is billed on 1,000 kVA — 18.8 percent more capacity for identical work. The usual cause is large inductive load — motors, compressors, chillers, lifts — running at low load factor with no correction, or with correction that has failed.Power factor and reactive power at the incomer and at each heavy motor load, over the full operating cycle rather than a spot reading.
One phase running noticeably hotter than the othersSingle-phase loads distributed unevenly across the three phases, which wastes capacity and stresses the neutral.Per-phase current at the board over time, so the imbalance is quantified and the rebalancing can be planned against figures.
Consumption that does not match what the site is doingUnmetered or unauthorised connections downstream of the measurement point, or a metering error.Measured consumption at the incomer reconciled against the sum of the sub-meters and against the utility bill.

Permanent meters and campaign analysers

The two record different things, and the distinction sets what the report can claim. Any proposal you receive should say which of them produced each finding.

Always on

Your permanent metering

The meters installed for energy monitoring already record the quality picture continuously: per-phase voltage and current, active, reactive and apparent power, power factor, supply frequency and phase loading. That gives trend and context — how power factor moves with production, whether imbalance is constant or shift-dependent.

Campaign

Power quality analysers

For harmonic distortion, voltage sags and swells, and transient events, calibrated power quality analysers are installed at the critical supply points — typically the main incomer, the transformer secondary and the feeds to the affected equipment — and logged for 7 to 30 days. The window is set to cover shift changes, start-up loads and grid events.

Client result

Fire risk identified

Voltage instability and unmetered load recorded — KCCA Usafi Market

Power quality monitoring at Kampala’s Usafi Market recorded load drawing on the market supply outside the metered distribution, and voltage instability at the distribution board severe enough to present a fire risk. Both were identified, quantified and reported to KCCA.

Read full case study

What the report delivers

  • Measurement record

    The full logged data set per measurement point — voltage profile, harmonic distortion, power factor and logged events — with the measurement window and instrument placement stated.

  • Event timeline

    Power quality events lined up against equipment trips, production interruptions and abnormal consumption, so cause and coincidence can be told apart.

  • Power factor correction case

    Where correction is justified, a capacitor bank specification sized from the measured reactive demand, with the payback shown against the charge it removes and the assumptions stated.

  • Remediation priority list

    Findings ranked by financial and operational impact against implementation effort, so your engineering team knows what to do first and what can wait for the next budget cycle.

Where a power factor charge is appearing on the bill, the correction case and the billing check usually run together — see utility bill verification.

Part of the monitoring service

This is one of the things Orijtech reads out of your monitoring data. It is not a separate installation and it needs no separate hardware.

How the monitoring works

Find out what is actually damaging your equipment

Tell us the symptom. The site survey decides where the instruments go.

Book a site assessment